| + | ====== UPS ====== | ||
| + | * {{: | ||
| + | ===== Jelalakok ===== | ||
| + | * https:// | ||
| + | |||
| + | {{: | ||
| + | |||
| + | |||
| + | ==== Négyszögjel ==== | ||
| + | * " | ||
| + | |||
| + | |||
| + | ==== Lépcsős színusz ==== | ||
| + | * " | ||
| + | * " | ||
| + | |||
| + | < | ||
| + | |||
| + | <note important> | ||
| + | ==== Tiszta színusz ==== | ||
| + | * "Sine wave" | ||
| + | * "Pure Sine Wave" | ||
| + | |||
| + | < | ||
| + | |||
| + | <note important> | ||
| + | |||
| + | |||
| + | ===== Topológiák ===== | ||
| + | * http:// | ||
| + | |||
| + | |||
| + | ==== Offline ==== | ||
| + | * " | ||
| + | |||
| + | |||
| + | ==== Vonal-interaktív ==== | ||
| + | * " | ||
| + | |||
| + | |||
| + | ==== Online ==== | ||
| + | * " | ||
| + | |||
| + | |||
| + | ===== Csúcsfeszültség-faktor ===== | ||
| + | * [[https:// | ||
| + | * [[http:// | ||
| + | |||
| + | < | ||
| + | The **crest factor** of an AC current waveform is the ratio of waveform' | ||
| + | crest factor = |peak current| / rms current | ||
| + | </ | ||
| + | |||
| + | The crest factor for a sinusoidal current waveform is 1.414 since the peak value of a true sinusoid is 1.414 times the rms value. Current waveforms for purely resistive loads are sinusoidal, so the crest factor will be 1.414. | ||
| + | |||
| + | Some loads, such as switching power supplies or lamp ballasts, have current waveforms that are not sinusoidal. They draw a high current for a short period of time, and their crest factors, therefore, can be quite a bit higher than 1.414. | ||
| + | |||
| + | Figure 1 shows current waveforms for two different loads, one sinusoidal (the blue trace) and one non-sinusoidal (the red trace). Both have an rms current of 5A, but as you can see the crest factor is quite different. | ||
| + | |||
| + | {{: | ||
| + | |||
| + | These two waveforms both have an rms current of 5 A, but their crest factors are very different. These two waveforms both have an rms current of 5 A, but their crest factors are very different. | ||
| + | As you would expect, the sinusoidal current waveform has a crest factor of 1.414: < | ||
| + | crest factor = |peak current| / rms current = 7.07 A / 5 A = 1.414 | ||
| + | </ | ||
| + | The non-sinusoidal current waveform, on the other hand, has a peak value of 21.21 A. The crest factor for this waveform is then: < | ||
| + | crest factor = |peak current| / rms current = 21.21 A / 5 A = 4.24 | ||
| + | </ | ||
| + | |||
| + | |||
| + | **Why is crest factor important? | ||
| + | |||
| + | In the examples shown in Figure 1, both loads draw the same amount of true power (assuming that the input voltage is the same for both). This means that a power source selected to feed the loads at 120VAC would need to provide the 600VA that both loads require. | ||
| + | |||
| + | A power source with a power output rating of 600VA may not, however, be able to provide the required peak currents that the non-sinusoidal load demands. When selecting an AC power source to power this load, you would need to choose a source possible of supply more than 21 A of peak current. In order to determine whether or not an AC source can handle high crest factor peak currents, look for the “peak repetitive current” or “crest factor” specifications in a power source' | ||
| + | < | ||
| + | </ | ||